Backflow assembly test · Station Grill
ApprovedFiled May 8, 2026 by Parker Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- May 8, 2026
- Assembly type
- RP
- Serial number
- Z195883
- Size
- 4
- Test gauge serial
- G-5476
- Gauge calibration date
- Jan 27, 2026
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-97-01310
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5937 Turkey Hill Dr
Owner: Danner Holdings LLC
Parcel 079-97-01310