Backflow assembly test · Corner Diner
ApprovedFiled Jun 18, 2024 by Parker Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- Jun 18, 2024
- Assembly type
- RP
- Serial number
- A205745
- Size
- 1 1/2
- Test gauge serial
- G-8374
- Gauge calibration date
- Oct 30, 2023
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-84-01070
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.