Back to the backflow review queue
Backflow assembly test: Corner Diner
ApprovedFiled Jun 25, 2026 by Parker Okafor, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 25, 2026
- Assembly type
- RP
- Serial number
- A205745
- Size
- 1 1/2
- Test gauge serial
- G-8144
- Gauge calibration date
- Oct 9, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 079-84-01070
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.