← Backflow review queue
Backflow assembly test · Corner Taqueria
ApprovedFiled Feb 6, 2024 by Reese Ashby, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Feb 6, 2024
- Assembly type
- RP
- Serial number
- B788854
- Size
- 4
- Test gauge serial
- G-4461
- Gauge calibration date
- Aug 5, 2023
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 083-62-01352
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2858 Spring Branch Rd
Owner: Lindqvist Holdings LLC
Parcel 083-62-01352