Backflow assembly test · 8650 Quarry Way
ApprovedFiled Jan 11, 2026 by Logan Danner, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 11, 2026
- Assembly type
- RP
- Serial number
- W667531
- Size
- 1
- Test gauge serial
- G-3513
- Gauge calibration date
- Aug 14, 2025
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-30-01200
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
8650 Quarry Way
Owner: Riley Stroud
Parcel 085-30-01200