Backflow assembly test · 177 Spring Branch Ct
ApprovedFiled Aug 12, 2025 by Hayden Danner, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 12, 2025
- Assembly type
- RP
- Serial number
- Z491759
- Size
- 1
- Test gauge serial
- G-7262
- Gauge calibration date
- Oct 30, 2024
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 085-56-01241
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.