Backflow assembly test · Hilltop Market
ApprovedFiled Jun 5, 2026 by Jordan Nguyen, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 5, 2026
- Assembly type
- DC
- Serial number
- Z823116
- Size
- 4
- Test gauge serial
- G-6350
- Gauge calibration date
- Nov 1, 2025
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-76-01267
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.