Backflow assembly test · 9451 Sycamore Rd
ApprovedFiled Aug 26, 2025 by Hayden Whitcomb, Patriot Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Aug 26, 2025
- Assembly type
- DC
- Serial number
- A249951
- Size
- 1
- Test gauge serial
- G-5716
- Gauge calibration date
- Apr 1, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-12-01120
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.