← Backflow review queue
Backflow assembly test · 7794 Hickory Ct
ApprovedFiled Sep 22, 2025 by Drew Vance, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 22, 2025
- Assembly type
- RP
- Serial number
- K188430
- Size
- 1
- Test gauge serial
- G-7755
- Gauge calibration date
- Jul 27, 2025
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-79-01130
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.