Backflow assembly test · 7794 Hickory Ct
ApprovedFiled Oct 11, 2026 by Drew Vance, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 11, 2026
- Assembly type
- RP
- Serial number
- K188430
- Size
- 1
- Test gauge serial
- G-8948
- Gauge calibration date
- Jun 7, 2026
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Vance, current on the service date
- All required fields present
- Address matches parcel 093-79-01130
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7794 Hickory Ct
Owner: Alex Pruitt
Parcel 093-79-01130