Backflow assembly test · 4781 Fox Run Way
ApprovedFiled Aug 23, 2025 by Reese Hollins, Lakeside Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Aug 23, 2025
- Assembly type
- RP
- Serial number
- Z946884
- Size
- 1
- Test gauge serial
- G-7716
- Gauge calibration date
- Dec 12, 2024
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 093-22-01079
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.