← Backflow review queue
Backflow assembly test · 184 Mill Creek Ct
Needs reviewFiled Nov 20, 2026 by Rowan Danner, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Nov 20, 2026
- Assembly type
- RP
- Serial number
- B861032
- Size
- 1
- Test gauge serial
- G-6803
- Gauge calibration date
- Jun 1, 2026
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 095-98-01342
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
184 Mill Creek Ct
Owner: Parker Lindqvist
Parcel 095-98-01342