← Backflow review queue
Backflow assembly test · 5597 Quarry Ln
ApprovedFiled Sep 16, 2025 by Quinn Ashby, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 16, 2025
- Assembly type
- RP
- Serial number
- W637735
- Size
- 3/4
- Test gauge serial
- G-1331
- Gauge calibration date
- Feb 20, 2025
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 095-93-01257
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5597 Quarry Ln
Owner: Drew Brandt
Parcel 095-93-01257