← Backflow review queue
Backflow assembly test · 8663 Mill Creek Trl
ApprovedFiled Jun 1, 2026 by Reese Whitcomb, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 1, 2026
- Assembly type
- RP
- Serial number
- W494081
- Size
- 1
- Test gauge serial
- G-7380
- Gauge calibration date
- Dec 8, 2025
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 095-33-01357
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8663 Mill Creek Trl
Owner: Riley Hollins
Parcel 095-33-01357