Backflow assembly test · 1308 Orchard Dr
ApprovedFiled May 26, 2025 by Morgan Benton, Keystone Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 26, 2025
- Assembly type
- RP
- Serial number
- K402657
- Size
- 3/4
- Test gauge serial
- G-5277
- Gauge calibration date
- Mar 23, 2025
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Benton, current on the service date
- All required fields present
- Address matches parcel 095-38-01249
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1308 Orchard Dr
Owner: Alex Pruitt
Parcel 095-38-01249