Backflow assembly test · 7472 Meadow Lark Trl
ApprovedFiled Apr 19, 2025 by Alex Kessler, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Apr 19, 2025
- Assembly type
- RP
- Serial number
- B705391
- Size
- 3/4
- Test gauge serial
- G-8743
- Gauge calibration date
- Dec 14, 2023
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-22-01031
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.