Backflow assembly test · 7681 Pine Knoll Trl
ApprovedFiled Oct 30, 2026 by Alex Kessler, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 30, 2026
- Assembly type
- RP
- Serial number
- K181791
- Size
- 3/4
- Test gauge serial
- G-6330
- Gauge calibration date
- Jun 4, 2026
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-94-01206
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7681 Pine Knoll Trl
Owner: Alex Marsh
Parcel 097-94-01206