Backflow assembly test · 6914 Turkey Hill Ln

Approved

Filed Jun 9, 2025 by Quinn Ramirez, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Jun 9, 2025
Assembly type
DC
Serial number
B183056
Size
1
Test gauge serial
G-4387
Gauge calibration date
Jan 26, 2025
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 097-30-01124
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6914 Turkey Hill Ln
Owner: Blake Lindqvist
Parcel 097-30-01124