Backflow assembly test · Golden Medical Offices
Needs reviewFiled Nov 25, 2026 by Taylor Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 25, 2026
- Assembly type
- RP
- Serial number
- Z567266
- Size
- 1
- Test gauge serial
- G-2347
- Gauge calibration date
- Jul 23, 2026
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-45-01324
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6922 Laurel Way
Owner: Benton Holdings LLC
Parcel 097-45-01324