Backflow assembly test · 7534 Pine Knoll Ct
ApprovedFiled Sep 20, 2026 by Drew Lindqvist, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Sep 20, 2026
- Assembly type
- RP
- Serial number
- A478890
- Size
- 3/4
- Test gauge serial
- G-1184
- Gauge calibration date
- Jun 17, 2026
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-50-01024
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.