Sonoma County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2806 Fox Run Ct

Approved

Filed Jun 15, 2024 by Taylor Whitcomb, Ridge Backflow Testing · filed from phone

Report

Date of service
Jun 15, 2024
Assembly type
RP
Serial number
A824283
Size
3/4
Test gauge serial
G-9853
Gauge calibration date
Mar 13, 2024
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 097-15-01097
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2806 Fox Run Ct
Owner: Taylor Whitcomb
Parcel 097-15-01097