Backflow assembly test: Main Street Taqueria

Approved

Filed May 11, 2025 by Morgan Pruitt, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 11, 2025
Assembly type
DC
Serial number
A581414
Size
1
Test gauge serial
G-5429
Gauge calibration date
Feb 28, 2025
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 107-21-01289
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5034 Quarry Trl
Owner: Brandt Holdings LLC
Parcel 107-21-01289