Tulare County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Market

Approved

Filed Oct 26, 2026 by Riley Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Oct 26, 2026
Assembly type
RP
Serial number
W638459
Size
1 1/2
Test gauge serial
G-2858
Gauge calibration date
May 11, 2026
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-64-01024
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5629 Ridgeview Way
Owner: Danner Holdings LLC
Parcel 107-64-01024