Backflow assembly test · 4581 Ridgeview Way
ApprovedFiled Apr 30, 2025 by Parker Fairley, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Apr 30, 2025
- Assembly type
- PVB
- Serial number
- W696721
- Size
- 3/4
- Test gauge serial
- G-9907
- Gauge calibration date
- Aug 5, 2024
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-83-01197
- Readings in range, no flags
- Result: passing. Next due date resets when approved.