Back to the backflow review queue
Backflow assembly test: 2410 Mill Creek Ln
ApprovedFiled Nov 12, 2026 by Emerson Wexler, Evergreen Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 12, 2026
- Assembly type
- DC
- Serial number
- W279515
- Size
- 1
- Test gauge serial
- G-4586
- Gauge calibration date
- May 14, 2026
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Wexler, current on the service date
- All required fields present
- Address matches parcel 111-50-01017
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
2410 Mill Creek Ln
Owner: Alex Brandt
Parcel 111-50-01017