Backflow assembly test · 3076 Cedar Hollow Way
ApprovedFiled Mar 13, 2025 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Mar 13, 2025
- Assembly type
- DC
- Serial number
- A875139
- Size
- 1
- Test gauge serial
- G-4111
- Gauge calibration date
- May 26, 2024
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-78-01260
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.