Backflow assembly test · 2579 Ridgeview Rd
Needs reviewFiled Nov 24, 2026 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Nov 24, 2026
- Assembly type
- DC
- Serial number
- Z352106
- Size
- 1
- Test gauge serial
- G-3132
- Gauge calibration date
- Sep 19, 2025
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-94-01151
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Property
2579 Ridgeview Rd
Owner: Alex Benton
Parcel 111-94-01151