Backflow assembly test · Riverside Grill
ApprovedFiled May 8, 2023 by Cameron Whitcomb, Evergreen Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 8, 2023
- Assembly type
- RP
- Serial number
- A254893
- Size
- 1
- Test gauge serial
- G-9510
- Gauge calibration date
- Dec 24, 2022
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-78-01196
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.