← Backflow review queue
Backflow assembly test · Riverside Bakery
ApprovedFiled May 1, 2026 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- May 1, 2026
- Assembly type
- RP
- Serial number
- A679043
- Size
- 1 1/2
- Test gauge serial
- G-8411
- Gauge calibration date
- Sep 3, 2025
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-97-01255
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2363 Quarry Ct
Owner: Ashby Holdings LLC
Parcel 111-97-01255