Backflow assembly test · 1563 Meadow Lark Dr
ApprovedFiled Jun 9, 2024 by Shawn Stroud, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 9, 2024
- Assembly type
- DC
- Serial number
- B214827
- Size
- 1
- Test gauge serial
- G-8293
- Gauge calibration date
- Mar 1, 2024
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-31-01309
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.