← Backflow review queue
Backflow assembly test · 8583 Old Church Ct
Needs reviewFiled Nov 24, 2026 by Casey Ramirez, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- K329856
- Size
- 1
- Test gauge serial
- G-9580
- Gauge calibration date
- May 1, 2026
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-38-01233
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.