← Backflow review queue
Backflow assembly test · 3873 Hickory Trl
ApprovedFiled Nov 23, 2025 by Jordan Harlow, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Nov 23, 2025
- Assembly type
- DC
- Serial number
- K682343
- Size
- 1
- Test gauge serial
- G-4896
- Gauge calibration date
- Apr 30, 2025
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-32-01164
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3873 Hickory Trl
Owner: Morgan Marsh
Parcel 113-32-01164