Yolo County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Diner

Approved

Filed Apr 1, 2025 by Rowan Harlow, Clearwater Backflow Testing · filed from phone

Report

Date of service
Apr 1, 2025
Assembly type
RP
Serial number
K737215
Size
1 1/2
Test gauge serial
G-4473
Gauge calibration date
Jun 20, 2024
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 113-84-01229
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7615 Turkey Hill Rd
Owner: Fairley Holdings LLC
Parcel 113-84-01229