← Backflow review queue
Backflow assembly test · Two Rivers Diner
ApprovedFiled Apr 1, 2025 by Rowan Harlow, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Apr 1, 2025
- Assembly type
- RP
- Serial number
- K737215
- Size
- 1 1/2
- Test gauge serial
- G-4473
- Gauge calibration date
- Jun 20, 2024
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-84-01229
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7615 Turkey Hill Rd
Owner: Fairley Holdings LLC
Parcel 113-84-01229