Backflow assembly test · 806 Ridgeview Ln
ApprovedFiled Mar 31, 2024 by Casey Ramirez, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Mar 31, 2024
- Assembly type
- RP
- Serial number
- W863241
- Size
- 1
- Test gauge serial
- G-5154
- Gauge calibration date
- Nov 15, 2023
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-64-01051
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
806 Ridgeview Ln
Owner: Blake Brandt
Parcel 113-64-01051