Backflow assembly test · 7864 Old Church Way
ApprovedFiled Apr 10, 2026 by Jordan Harlow, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 10, 2026
- Assembly type
- DC
- Serial number
- K171690
- Size
- 3/4
- Test gauge serial
- G-8648
- Gauge calibration date
- Nov 27, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-61-01329
- Readings in range, no flags
- Result: passing. Next due date resets when approved.