Backflow assembly test · 7540 Cedar Hollow Ln
ApprovedFiled Dec 10, 2023 by Rowan Harlow, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Dec 10, 2023
- Assembly type
- DC
- Serial number
- K635522
- Size
- 1
- Test gauge serial
- G-3156
- Gauge calibration date
- Dec 11, 2022
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-43-01069
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.