← Backflow review queue
Backflow assembly test · 217 Orchard Ln
ApprovedFiled Jan 21, 2025 by Logan Ramirez, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 21, 2025
- Assembly type
- RP
- Serial number
- W154219
- Size
- 3/4
- Test gauge serial
- G-8437
- Gauge calibration date
- Jul 6, 2024
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-81-01093
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
217 Orchard Ln
Owner: Rowan Calloway
Parcel 001-81-01093