Backflow assembly test · Station Self Storage

Approved

Filed Feb 20, 2026 by Logan Ramirez, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Feb 20, 2026
Assembly type
RP
Serial number
K959390
Size
4
Test gauge serial
G-8040
Gauge calibration date
May 19, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-99-01276
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

588 Laurel Trl
Owner: Benton Holdings LLC
Parcel 001-99-01276