← Backflow review queue
Backflow assembly test · Two Rivers Taqueria
ApprovedFiled May 23, 2024 by Quinn Fairley, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- May 23, 2024
- Assembly type
- RP
- Serial number
- Z829068
- Size
- 2
- Test gauge serial
- G-8788
- Gauge calibration date
- Apr 13, 2024
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-88-01017
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4463 Sycamore Dr
Owner: Ashby Holdings LLC
Parcel 001-88-01017