Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Dental

Approved

Filed Mar 20, 2026 by Logan Ramirez, Keystone Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Mar 20, 2026
Assembly type
RP
Serial number
K504853
Size
2
Test gauge serial
G-8661
Gauge calibration date
Jun 15, 2025
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-36-01098
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4731 Turkey Hill Ln
Owner: Whitcomb Holdings LLC
Parcel 001-36-01098