Backflow assembly test · Blue Heron Apartments
ApprovedFiled Nov 18, 2024 by Rowan Marsh, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 18, 2024
- Assembly type
- DC
- Serial number
- B878179
- Size
- 1 1/2
- Test gauge serial
- G-2462
- Gauge calibration date
- Sep 1, 2023
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-38-01043
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4979 Hickory Way
Owner: Harlow Holdings LLC
Parcel 001-38-01043