Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Animal Hospital

Approved

Filed Aug 29, 2026 by Rowan Marsh, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Aug 29, 2026
Assembly type
RP
Serial number
A667205
Size
1 1/2
Test gauge serial
G-7810
Gauge calibration date
Feb 20, 2026
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-80-01317
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4788 Pine Knoll Way
Owner: Kessler Holdings LLC
Parcel 001-80-01317