Backflow assembly test · 8855 Mill Creek Ln
ApprovedFiled Jul 23, 2025 by Cameron Kessler, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Jul 23, 2025
- Assembly type
- PVB
- Serial number
- W484918
- Size
- 3/4
- Test gauge serial
- G-3822
- Gauge calibration date
- Jul 4, 2024
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-58-01195
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8855 Mill Creek Ln
Owner: Shawn Ramirez