Backflow assembly test · 4470 Meadow Lark Rd
ApprovedFiled Jul 4, 2025 by Shawn Hollins, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 4, 2025
- Assembly type
- DC
- Serial number
- A847508
- Size
- 1
- Test gauge serial
- G-1557
- Gauge calibration date
- Dec 29, 2024
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-39-01071
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.