Backflow assembly test · 6740 Orchard Ct

Approved

Filed Mar 15, 2026 by Drew Fairley, Evergreen Backflow Testing · filed from phone

Report

Date of service
Mar 15, 2026
Assembly type
PVB
Serial number
B802471
Size
1
Test gauge serial
G-8698
Gauge calibration date
Jul 27, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-76-01095
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.