Backflow assembly test · 8023 Laurel Rd
ApprovedFiled Nov 9, 2024 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Nov 9, 2024
- Assembly type
- RP
- Serial number
- A999924
- Size
- 3/4
- Test gauge serial
- G-9283
- Gauge calibration date
- Mar 10, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-53-01284
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8023 Laurel Rd
Owner: Cameron Ramirez
Parcel 013-53-01284