Backflow assembly test · 3404 Pine Knoll Ln
ApprovedFiled Oct 14, 2024 by Cameron Kessler, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Oct 14, 2024
- Assembly type
- RP
- Serial number
- K785094
- Size
- 1
- Test gauge serial
- G-4340
- Gauge calibration date
- Dec 21, 2023
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-51-01355
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.