Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 880 Turkey Hill Trl

Approved

Filed Jun 11, 2024 by Cameron Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Jun 11, 2024
Assembly type
RP
Serial number
W417511
Size
3/4
Test gauge serial
G-8199
Gauge calibration date
Aug 17, 2023
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-13-01248
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

880 Turkey Hill Trl
Owner: Casey Ellery
Parcel 013-13-01248