← Backflow review queue
Backflow assembly test · 7505 Laurel Way
ApprovedFiled Aug 14, 2025 by Shawn Hollins, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 14, 2025
- Assembly type
- DC
- Serial number
- Z356666
- Size
- 3/4
- Test gauge serial
- G-9735
- Gauge calibration date
- Mar 21, 2025
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-97-01042
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7505 Laurel Way
Owner: Cameron Fairley
Parcel 013-97-01042