Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Grill

Approved

Filed Aug 21, 2024 by Cameron Kessler, Northstar Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Aug 21, 2024
Assembly type
RP
Serial number
K839582
Size
1 1/2
Test gauge serial
G-3053
Gauge calibration date
Jan 5, 2024
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-17-01184
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

477 Ridgeview Dr
Owner: Fairley Holdings LLC
Parcel 013-17-01184